Skip to main content

P 65 B

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
60.00
kVA
Continuous power (PRP)
48.00
kW
Stand-by power (LTP)
63.00
kVA
Stand-by power (LTP)
50.40
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 60 Hz
Voltage (V) 220 VAC

DIMENSIONS AND NOISE

Width 960 mm
Length 1750 mm
Height 1375 mm
Weight 930 kg

AWESOME FEATURES

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model P 65 B
Connection Series delta
DIMENSIONS AND NOISE
Width 960 mm
Length 1750 mm
Height 1375 mm
Weight 930 kg
ENGINE BASE DATA
Description PERKINS
Engine model 1103A-33TG2
P.R.P. Power 68.1 kVA
L.T.P. Power 75.1 kVA
Cylinders 3.0
Speed 1800.0 r.p.m.
Cubic capacity 3.3 l
Air intake Turbocharged
Standard voltage 12.0 Vdc
Optional voltage 24.0 Vdc
Sae 3-11«
BMEP 1279.0 kPa
Cooling Water
Fuel Cons. at 100% (L.T.P.) 18.2 l/h
Fuel Cons. at 100% (P.R.P) 16.6 l/h
Fuel Cons. at 75% (P.R.P.) 12.5 l/h
Fuel Cons. at 50% (P.R.P.) 8.8 l/h
Fuel Cons. at 25% (P.R.P.) 5.1 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Not available
SPEED REGULATION
Electronic regulator On request
Precision class G2
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 8.3 l
Engine Antifreeze capacity 4.4 l
Radiator antifreeze capacity 5.8 l
Total amount of antifreeze 10.2 l
HEAT FROM ENGINE
Heat from radiator 41.0 kW
Heat from exhaust 52.0 kW
Heat from radiation 11.0 kW
HEAT FROM EXHAUST
Exhaust temperature 534 °C
Cooling air flow 111 m³/min
Combustion air flow 4.7 m³/min
Exhaust gas flow 11.8 m³/min
GENERAL ALTERNATOR DATA
Description DINGOL
Alternator model DG60
L.T.P. Power 63 kVA
P.R.P. Power 60 kVA
ALTERNATOR WIRINGS
Connection Series delta
Phases 3F
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator 460
Precision 2 ± %
RADIATOR
Radiator antifreeze capacity 5.8 l
BASEFRAME DATA
Model T1
Standard tank 160 l
CANOPY DATA
Canopy model SENZA COFANO
Silencer model MS 12
Silencer outlet diameter 60 mm

STANDARD CONTROL PANEL

CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA

USER MENU