P 105 GX
DATASHEET PDF
NEED MORE INFO?
MAIN DATA
Continuous power (PRP) |
100.00
|
kVA |
Continuous power (PRP) |
80.00
|
kW |
Stand-by power (LTP) |
110.00
|
kVA |
Stand-by power (LTP) |
88.00
|
kW |
Power factor | 0.8 | cos(fi) |
Frequency (Hz) | 50 | Hz |
Voltage (V) | 380 | VAC |
DIMENSIONS AND NOISE
Width | 1040 | mm |
Length | 2560 | mm |
Height | 1805 | mm |
Weight | 1630 | kg |
AWESOME FEATURES
TECHNICAL DATA
GEN SET GENERAL DATA | ||
---|---|---|
Genset model | P 105 GX | |
Connection | Series star |
DIMENSIONS AND NOISE | ||
---|---|---|
Width | 1040 | mm |
Length | 2560 | mm |
Height | 1805 | mm |
Weight | 1630 | kg |
ENGINE BASE DATA | ||
---|---|---|
Description | PERKINS | |
Engine model | 1104C-44TAG2 | |
P.R.P. Power | 100.0 | kVA |
L.T.P. Power | 110.0 | kVA |
Cylinders | 4.0 | |
Speed | 1500.0 | r.p.m. |
Cubic capacity | 4.4 | l |
Air intake | Turbocharged | |
Standard voltage | 12.0 | Vdc |
Optional voltage | 24.0 | Vdc |
Sae | 3-11« | |
BMEP | 1702.0 | kPa |
Cooling | Water | |
Fuel Cons. at 100% (L.T.P.) | 24.9 | l/h |
Fuel Cons. at 100% (P.R.P) | 22.6 | l/h |
Fuel Cons. at 75% (P.R.P.) | 17.1 | l/h |
Fuel Cons. at 50% (P.R.P.) | 11.2 | l/h |
Fuel Cons. at 25% (P.R.P.) | 0.0 | l/h |
EMISSIONS | ||
---|---|---|
TA Luft | Not available | |
TA Luft/2 | Not available | |
EPA | Not available | |
Stage | Stage 2 |
SPEED REGULATION | ||
---|---|---|
Electronic regulator | Standard | |
Precision class | G3 |
ENGINE DIMENSIONS AND LIQUIDS | ||
---|---|---|
Oil quantity | 8.0 | l |
Engine Antifreeze capacity | 7.0 | l |
Radiator antifreeze capacity | 5.6 | l |
Total amount of antifreeze | 12.6 | l |
HEAT FROM ENGINE | ||
---|---|---|
Heat from radiator | 46.1 | kW |
Heat from exhaust | 71.7 | kW |
Heat from radiation | 6.8 | kW |
HEAT FROM EXHAUST | ||
---|---|---|
Exhaust temperature | 514 | °C |
Cooling air flow | 165.6 | m³/min |
Combustion air flow | 6.01 | m³/min |
Exhaust gas flow | 15.2 | m³/min |
GENERAL ALTERNATOR DATA | ||
---|---|---|
Description | DINGOL | |
Alternator model | DG100 | |
L.T.P. Power | 110 | kVA |
P.R.P. Power | 100 | kVA |
ALTERNATOR WIRINGS | ||
---|---|---|
Connection | Series star | |
Phases | 3F+N | |
Winding | 12 terminals Winding 311 | |
Terminal Number | 12 | nr. |
ALTERNATOR PROTECTION | ||
---|---|---|
IP Protection | 23 |
ALTERNATOR REGULATOR | ||
---|---|---|
Electronic regulator | 460 | |
Precision | 2 | ± % |
RADIATOR | ||
---|---|---|
Radiator antifreeze capacity | 5.6 | l |
BASEFRAME DATA | ||
---|---|---|
Model | GV060HD | |
Standard tank | 160 | l |
CANOPY DATA | ||
---|---|---|
Canopy model | GV060 | |
Silencer model | MSR/a 65 | |
Silencer outlet diameter | 76 | mm |
STANDARD CONTROL PANEL
CONTROL PANEL DATA | ||
---|---|---|
Description | GUARD REVOLUTION AUTO |
STANDARD ATS
ATS PANEL DATA | ||
---|---|---|
Description | ATS-C 160 |