web supervisor

FOX - P 14 FOX

Error message

Notice: Undefined variable: links in wl_genset_view() (line 4372 of /srv/www/www71.visa.it/web/sites/all/modules/custom/wl_genset/wl_genset.module).

Characteristics

110000000145-000-00.jpg
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
Standard genset technical data sheet
IT EN DE FR RU ES
Standard control panel technical datasheet
Gen Set performance
0.0
kVA
0.0
kW
0.0
kVA
0.0
kW
0.8
60
Hz
380
V
Dimensions and noise level
770
mm
1660
mm
1330
mm
580
kg

Technical datasheet

Engine
General engine data
PERKINS
403A-15G1
3
1800
r.p.m.
1.50
l
Aspirated
12
Vdc
Vdc
4-7½
650
kPa
Water
Engine power
14.4
kW
15.9
kW
Fuel consumption
4.8
l/h
4.3
l/h
3.3
l/h
2.4
l/h
0.0
l/h
Speed regulation
On request
G2
Engine dimensions and liquids
6.0
l
2.6
l
3.4
l
6.0
l
Heat from engine
13.6
kW
10.3
kW
4.0
kW
Heat from exhaust
455
°C
34.80
m³/min
1.23
m³/min
3.14
m³/min
Emissions
Not available
Not available
Not available
Not available
Alternator
General alternator data
MECC ALTE
ECP3-2L/4
0.0
kVA
0.0
kVA
Alternator wirings
Series star
3PH+N
12 terminals std
12
nr.
Alternator protection
23
Alternator regulator
DSR
1.0
± %
Baseframe - Canopy - Exhaust muffler
Baseframe data
FOX
FOX
50
l
600
l
0
l
Canopy & Exhaust muffler
FOX
MSR/a 35
45.0
mm

Accessories

ATS changeover switch panel
ATS-C 45
110000000142-000-00.png
ATS is a new line of changeover switch panels developed and manufactured by Visa S.P.A. in accordance with CEI EN 61439-2 (construction standard). Specifically used for generating sets, the changeover switch panel allows the changeover between mains/genset or genset/genset. The main part of the panel contains two interlocking contactors or a motorised circuit breaker. All of the parts are installed inside a sturdy powder-coated metal box (RAL7035) and equipped with a lock to close the access door.

Star

With star the start of each of the three phases is connected together. Connections are taken from the ends of the three phases to give the three phases
Star symbol voltage

Delta

With Delta the starts and ends of the phases are connected. The end of phase 1 is connected to the start of phase 2, the end of phase 2 to the start of phase 3, and the end of phase 3 to the start of phase 1. Connections are taken from the three start-end points to give the three phases.
Delta symbol voltage
newsletter subscription