Skip to main content

F 400 GX C13TE3A S4L1D-F 400 V 50 HZ

DATASHEET PDF

NEED MORE INFO?

Fill the form with all your requests

ASK FOR A QUOTATION

MAIN DATA

Continuous power (PRP)
400.00
kVA
Continuous power (PRP)
320.00
kW
Emergency power (E.P.)
440.00
kVA
Emergency power (E.P.)
352.00
kW
Power factor 0.8 cos(fi)
Frequency (Hz) 50 Hz
Voltage (V) 400 VAC

DIMENSIONS AND NOISE

Width 1600 mm
Length 4310 mm
Height 2560 mm
Weight 4750 kg
Sound pressure 7 m. 70.0 dBA

AWESOME FEATURES

TECHNICAL DATA

GEN SET GENERAL DATA
Genset model F 400 GX
Connection Series star
DIMENSIONS AND NOISE
Width 1600 mm
Length 4310 mm
Height 2560 mm
Weight 4750 kg
Sound pressure 7 m. 70.0 dBA
ENGINE BASE DATA
Description FPT IVECO
Engine model C13TE3A
P.R.P. Power 400.0 kVA
E.P. Power 440.0 kVA
Cylinders 6.0
Speed 1500.0 r.p.m.
Cubic capacity 12.9 l
Air intake Turbocharged
Standard voltage 24.0 Vdc
Optional voltage Vdc
Sae 1-14
BMEP 2259.0 kPa
Cooling Water
Fuel Cons. at 100% (E.P.) 98.5 l/h
Fuel Cons. at 100% (P.R.P) 87.5 l/h
Fuel Cons. at 75% (P.R.P.) 68.0 l/h
Fuel Cons. at 50% (P.R.P.) 48.6 l/h
Fuel Cons. at 25% (P.R.P.) 0.0 l/h
EMISSIONS
TA Luft Not available
TA Luft/2 Not available
EPA Not available
Stage Stage 2
SPEED REGULATION
Electronic regulator Standard
Precision class G3
ENGINE DIMENSIONS AND LIQUIDS
Oil quantity 35.0 l
Engine Antifreeze capacity 19.5 l
Radiator antifreeze capacity 47.5 l
Total amount of antifreeze 67 l
HEAT FROM ENGINE
Heat from radiator 157.6 kW
Heat from exhaust 299.5 kW
Heat from radiation 13.6 kW
HEAT FROM EXHAUST
Exhaust temperature 445.0 °C
Combustion air flow 29.5 m³/min
Exhaust gas flow 76.7 m³/min
GENERAL ALTERNATOR DATA
Description STAMFORD
Alternator model S4L1D-F
E.P. Power 465.0 kVA
P.R.P. Power 415.0 kVA
ALTERNATOR WIRINGS
Connection Series star
Phases 3F+N
Winding 12 terminals Winding 311
Terminal Number 12 nr.
ALTERNATOR PROTECTION
IP Protection 23
ALTERNATOR REGULATOR
Electronic regulator AS440
Precision 1.0 ± %
RADIATOR
Radiator antifreeze capacity 47.5 l
BASEFRAME DATA
Model GV151/00/00
Standard tank 800 l
CANOPY DATA
Canopy model GV151
Silencer model MSR/a 125
Silencer outlet diameter 140.0 mm

STANDARD CONTROL PANEL

CONTROL PANEL DATA
Description GUARD REVOLUTION AUTO

STANDARD ATS

ATS PANEL DATA
Description ATS-M 630

user icon menu

USER MENU

User not logged in