C 1250 S KTA50-G3 PI734A 480 V 60 HZ
DATASHEET PDF
NEED MORE INFO?
MAIN DATA
| Continuous power (PRP) |
1420.00
|
kVA |
| Continuous power (PRP) |
1136.00
|
kW |
| Emergency power (E.P.) |
1600.00
|
kVA |
| Emergency power (E.P.) |
1280.00
|
kW |
| Power factor | 0.8 | cos(fi) |
| Frequency (Hz) | 60 | Hz |
| Voltage (V) | 480 | VAC |
DIMENSIONS AND NOISE
| Width | 2200 | mm |
| Length | 8600 | mm |
| Height | 3400 | mm |
| Weight | 14870 | kg |
| Sound pressure 7 m. | 79.0 | dBA |
AWESOME FEATURES
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
TECHNICAL DATA
| GEN SET GENERAL DATA | ||
|---|---|---|
| Genset model | C 1250 S | |
| Connection | Star | |
| DIMENSIONS AND NOISE | ||
|---|---|---|
| Width | 2200 | mm |
| Length | 8600 | mm |
| Height | 3400 | mm |
| Weight | 14870 | kg |
| Sound pressure 7 m. | 79.0 | dBA |
| ENGINE BASE DATA | ||
|---|---|---|
| Description | CUMMINS | |
| Engine model | KTA50-G3 | |
| P.R.P. Power | 1420.0 | kVA |
| E.P. Power | 1600.0 | kVA |
| Cylinders | 16.0 | |
| Speed | 1800.0 | r.p.m. |
| Cubic capacity | 50.3 | l |
| Air intake | Turbocharged | |
| Standard voltage | 24.0 | Vdc |
| Optional voltage | Vdc | |
| Sae | 0-18 | |
| BMEP | 1620.0 | kPa |
| Cooling | Water | |
| Fuel Cons. at 100% (E.P.) | 330.0 | l/h |
| Fuel Cons. at 100% (P.R.P) | 291.0 | l/h |
| Fuel Cons. at 75% (P.R.P.) | 222.0 | l/h |
| Fuel Cons. at 50% (P.R.P.) | 157.0 | l/h |
| Fuel Cons. at 25% (P.R.P.) | 89.0 | l/h |
| EMISSIONS | ||
|---|---|---|
| TA Luft | Not available | |
| TA Luft/2 | Not available | |
| EPA | Not available | |
| Stage | Not available | |
| SPEED REGULATION | ||
|---|---|---|
| Electronic regulator | Standard | |
| Precision class | G3 | |
| ENGINE DIMENSIONS AND LIQUIDS | ||
|---|---|---|
| Oil quantity | 177.0 | l |
| Engine Antifreeze capacity | 161.0 | l |
| Radiator antifreeze capacity | 152.0 | l |
| Total amount of antifreeze | 313 | l |
| HEAT FROM ENGINE | ||
|---|---|---|
| Heat from radiator | 900.0 | kW |
| Heat from exhaust | 935.0 | kW |
| Heat from radiation | 150.0 | kW |
| HEAT FROM EXHAUST | ||
|---|---|---|
| Exhaust temperature | 176.0 | °C |
| Combustion air flow | 110.4 | m³/min |
| Exhaust gas flow | 257.7 | m³/min |
| GENERAL ALTERNATOR DATA | ||
|---|---|---|
| Description | STAMFORD | |
| Alternator model | PI734A | |
| E.P. Power | 1630.0 | kVA |
| P.R.P. Power | 1525.0 | kVA |
| ALTERNATOR WIRINGS | ||
|---|---|---|
| Connection | Star | |
| Phases | 3F+N | |
| Winding | 6 terminals winding 312 | |
| Terminal Number | 6 | nr. |
| ALTERNATOR PROTECTION | ||
|---|---|---|
| IP Protection | 23 | |
| ALTERNATOR REGULATOR | ||
|---|---|---|
| Electronic regulator | MX341 | |
| Precision | 1.0 | ± % |
| RADIATOR | ||
|---|---|---|
| Radiator antifreeze capacity | 152.0 | l |
| BASEFRAME DATA | ||
|---|---|---|
| Model | ST60 | |
| Standard tank | 0 | l |
| CANOPY DATA | ||
|---|---|---|
| Canopy model | C60/05/01 | |
| Silencer model | MSR/a 200 | |
| Silencer outlet diameter | 219.0 | mm |
STANDARD CONTROL PANEL
| CONTROL PANEL DATA | ||
|---|---|---|
| Description | GUARD REVOLUTION AUTO | |
STANDARD ATS
| ATS PANEL DATA |
|---|