P 620 GX 2506C-E15TAG4 S5L1D-F 380 V 60 HZ

DATASHEET PDF
NEED MORE INFO?
MAIN DATA
| Continuous power (PRP) | 0.00 | kVA | 
| Continuous power (PRP) | 0.00 | kW | 
| Emergency power (E.P.) | 687.00 | kVA | 
| Emergency power (E.P.) | 549.60 | kW | 
| Power factor | 0.8 | cos(fi) | 
| Frequency (Hz) | 60 | Hz | 
| Voltage (V) | 380 | VAC | 
DIMENSIONS AND NOISE
| Sound pressure 7 m. | 76.0 | dBA | 
AWESOME FEATURES
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
                           2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
TECHNICAL DATA
| GEN SET GENERAL DATA | ||
|---|---|---|
| Genset model | P 620 GX | |
| Connection | Series star | |
| DIMENSIONS AND NOISE | ||
|---|---|---|
| Sound pressure 7 m. | 76.0 | dBA | 
| ENGINE BASE DATA | ||
|---|---|---|
| Description | PERKINS | |
| Engine model | 2506C-E15TAG4 | |
| P.R.P. Power | 0.0 | kVA | 
| E.P. Power | 687.0 | kVA | 
| Cylinders | 6.0 | |
| Speed | 1800.0 | r.p.m. | 
| Cubic capacity | 15.2 | l | 
| Air intake | Turbocharged | |
| Standard voltage | 24.0 | Vdc | 
| Optional voltage | Vdc | |
| Sae | ½-14 | |
| BMEP | 2769.0 | kPa | 
| Cooling | Water | |
| Fuel Cons. at 100% (E.P.) | 146.0 | l/h | 
| Fuel Cons. at 100% (P.R.P) | 0.0 | l/h | 
| Fuel Cons. at 75% (P.R.P.) | 0.0 | l/h | 
| Fuel Cons. at 50% (P.R.P.) | 0.0 | l/h | 
| Fuel Cons. at 25% (P.R.P.) | 0.0 | l/h | 
| EMISSIONS | ||
|---|---|---|
| TA Luft | Not available | |
| TA Luft/2 | Not available | |
| EPA | Not available | |
| Stage | Not available | |
| SPEED REGULATION | ||
|---|---|---|
| Electronic regulator | Standard | |
| Precision class | G3 | |
| ENGINE DIMENSIONS AND LIQUIDS | ||
|---|---|---|
| Oil quantity | 62.0 | l | 
| Engine Antifreeze capacity | 0.0 | l | 
| Radiator antifreeze capacity | 58.0 | l | 
| Total amount of antifreeze | 58 | l | 
| HEAT FROM ENGINE | ||
|---|---|---|
| Heat from radiator | 195.0 | kW | 
| Heat from exhaust | 540.0 | kW | 
| Heat from radiation | 26.5 | kW | 
| HEAT FROM EXHAUST | ||
|---|---|---|
| Exhaust temperature | 550.0 | °C | 
| Combustion air flow | 42.0 | m³/min | 
| Exhaust gas flow | 120.0 | m³/min | 
| GENERAL ALTERNATOR DATA | ||
|---|---|---|
| Description | STAMFORD | |
| Alternator model | S5L1D-F | |
| E.P. Power | 738.0 | kVA | 
| P.R.P. Power | 673.0 | kVA | 
| ALTERNATOR WIRINGS | ||
|---|---|---|
| Connection | Series star | |
| Phases | 3F+N | |
| Winding | 12 terminals Winding 311 | |
| Terminal Number | 12 | nr. | 
| ALTERNATOR PROTECTION | ||
|---|---|---|
| IP Protection | 23 | |
| ALTERNATOR REGULATOR | ||
|---|---|---|
| Electronic regulator | AS440 | |
| Precision | 1.0 | ± % | 
| RADIATOR | ||
|---|---|---|
| Radiator antifreeze capacity | 58.0 | l | 
| BASEFRAME DATA | ||
|---|---|---|
| Model | GV201 | |
| Standard tank | 950 | l | 
| CANOPY DATA | ||
|---|---|---|
| Canopy model | GV201/00/1 | |
| Silencer model | MSR/a 150 | |
| Silencer outlet diameter | 168.0 | mm | 
STANDARD CONTROL PANEL
| CONTROL PANEL DATA | 
|---|
STANDARD ATS
ATS is a new line of changeover switch panels developed and manufactured  by Visa S.P.A. in accordance with CEI EN 61439-2 (construction standard). Specifically used for generating sets, the changeover switch panel allows the changeover between mains/genset or genset/genset. The main part of the panel contains two interlocking contactors or a motorised circuit breaker. All of the parts are installed inside a sturdy powder-coated metal box (RAL7035) and equipped with a lock to close the access door. 
                                                      | ATS PANEL DATA | ||
|---|---|---|
| Description | ATS-C 45 | |
 
        
    