V 250 GX TAD841GE UCI274H 480 V 60 HZ
DATASHEET PDF
NEED MORE INFO?
MAIN DATA
Continuous power (PRP) |
255.00
|
kVA |
Continuous power (PRP) |
204.00
|
kW |
Emergency power (E.P.) |
280.00
|
kVA |
Emergency power (E.P.) |
224.00
|
kW |
Power factor | 0.8 | cos(fi) |
Frequency (Hz) | 60 | Hz |
Voltage (V) | 480 | VAC |
DIMENSIONS AND NOISE
Sound pressure 7 m. | 74.0 | dBA |
AWESOME FEATURES
TECHNICAL DATA
GEN SET GENERAL DATA | ||
---|---|---|
Genset model | V 250 GX | |
Connection | Series star |
DIMENSIONS AND NOISE | ||
---|---|---|
Sound pressure 7 m. | 74.0 | dBA |
ENGINE BASE DATA | ||
---|---|---|
Description | VOLVO-PENTA | |
Engine model | TAD841GE | |
P.R.P. Power | 259.0 | kVA |
E.P. Power | 285.0 | kVA |
Cylinders | 6.0 | |
Speed | 1800.0 | r.p.m. |
Cubic capacity | 7.7 | l |
Air intake | Turbocharged | |
Standard voltage | 24.0 | Vdc |
Optional voltage | Vdc | |
Sae | 2-11½ | |
BMEP | 0.0 | kPa |
Cooling | Water | |
Fuel Cons. at 100% (E.P.) | 64.8 | l/h |
Fuel Cons. at 100% (P.R.P) | 59.5 | l/h |
Fuel Cons. at 75% (P.R.P.) | 45.3 | l/h |
Fuel Cons. at 50% (P.R.P.) | 32.1 | l/h |
Fuel Cons. at 25% (P.R.P.) | 17.1 | l/h |
EMISSIONS | ||
---|---|---|
TA Luft | Not available | |
TA Luft/2 | Not available | |
EPA | Not available | |
Stage | Not available |
SPEED REGULATION | ||
---|---|---|
Electronic regulator | Standard | |
Precision class | G3 |
ENGINE DIMENSIONS AND LIQUIDS | ||
---|---|---|
Oil quantity | 27.0 | l |
Engine Antifreeze capacity | 17.0 | l |
Radiator antifreeze capacity | 19.0 | l |
Total amount of antifreeze | 36 | l |
HEAT FROM ENGINE | ||
---|---|---|
Heat from radiator | 0.0 | kW |
Heat from exhaust | 0.0 | kW |
Heat from radiation | 0.0 | kW |
HEAT FROM EXHAUST | ||
---|---|---|
Exhaust temperature | 435.0 | °C |
Combustion air flow | 20.5 | m³/min |
Exhaust gas flow | 0.0 | m³/min |
GENERAL ALTERNATOR DATA | ||
---|---|---|
Description | STAMFORD | |
Alternator model | UCI274H | |
E.P. Power | 280.0 | kVA |
P.R.P. Power | 255.0 | kVA |
ALTERNATOR WIRINGS | ||
---|---|---|
Connection | Series star | |
Phases | 3F+N | |
Winding | 12 terminals Winding 311 | |
Terminal Number | 12 | nr. |
ALTERNATOR PROTECTION | ||
---|---|---|
IP Protection | 23 |
ALTERNATOR REGULATOR | ||
---|---|---|
Electronic regulator | AS440 | |
Precision | 1.0 | ± % |
RADIATOR | ||
---|---|---|
Radiator antifreeze capacity | 19.0 | l |
BASEFRAME DATA | ||
---|---|---|
Model | GV121 | |
Standard tank | 500 | l |
CANOPY DATA | ||
---|---|---|
Canopy model | GV121/00/1 | |
Silencer model | MSR/a 100 | |
Silencer outlet diameter | 114.0 | mm |
STANDARD CONTROL PANEL
CONTROL PANEL DATA | ||
---|---|---|
Description | GUARD REVOLUTION AUTO |
STANDARD ATS
ATS PANEL DATA |
---|