V 500 GX TAD1346GE S5L1D-C 220 V 60 HZ

DATASHEET PDF
NEED MORE INFO?
MAIN DATA
| Continuous power (PRP) |
510.00
|
kVA |
| Continuous power (PRP) |
408.00
|
kW |
| Emergency power (E.P.) |
560.00
|
kVA |
| Emergency power (E.P.) |
448.00
|
kW |
| Power factor | 0.8 | cos(fi) |
| Frequency (Hz) | 60 | Hz |
| Voltage (V) | 220 | VAC |
DIMENSIONS AND NOISE
AWESOME FEATURES
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
2- Industrial brushless alternator with AVR
3- Steel baseframe with retention basin, fuel tank with level sensor
4- Soundproof canopy in galvanised, power coated sheet steel
5- Soundproofing material made of high attenuation polyester fibre
6- Internal exhaust silencer with insulated manifold
7- Electrical panel mounted on board the unit with digital control device installed in metal box
8- Compact for easy handling and use
9- Test report, manuals and electrical drawings supplied
10- World wide after sales service and technical support
Further details on the technical data sheet
TECHNICAL DATA
| GEN SET GENERAL DATA | ||
|---|---|---|
| Genset model | V 500 GX | |
| Connection | Parallel star | |
| DIMENSIONS AND NOISE |
|---|
| ENGINE BASE DATA | ||
|---|---|---|
| Description | VOLVO-PENTA | |
| Engine model | TAD1346GE | |
| P.R.P. Power | 510.0 | kVA |
| E.P. Power | 560.0 | kVA |
| Cylinders | 6.0 | |
| Speed | 1800.0 | r.p.m. |
| Cubic capacity | 12.8 | l |
| Air intake | Turbocharged | |
| Standard voltage | 24.0 | Vdc |
| Optional voltage | Vdc | |
| Sae | 1-14 | |
| BMEP | 0.0 | kPa |
| Cooling | Water | |
| Fuel Cons. at 100% (E.P.) | 116.7 | l/h |
| Fuel Cons. at 100% (P.R.P) | 106.6 | l/h |
| Fuel Cons. at 75% (P.R.P.) | 81.6 | l/h |
| Fuel Cons. at 50% (P.R.P.) | 54.7 | l/h |
| Fuel Cons. at 25% (P.R.P.) | 24.4 | l/h |
| EMISSIONS | ||
|---|---|---|
| TA Luft | Not available | |
| TA Luft/2 | Not available | |
| EPA | Not available | |
| Stage | Stage 2 | |
| SPEED REGULATION | ||
|---|---|---|
| Electronic regulator | Standard | |
| Precision class | G3 | |
| ENGINE DIMENSIONS AND LIQUIDS | ||
|---|---|---|
| Oil quantity | 36.0 | l |
| Engine Antifreeze capacity | 48.0 | l |
| Radiator antifreeze capacity | 28.0 | l |
| Total amount of antifreeze | 76 | l |
| HEAT FROM ENGINE | ||
|---|---|---|
| Heat from radiator | 135.0 | kW |
| Heat from exhaust | 316.0 | kW |
| Heat from radiation | 23.0 | kW |
| HEAT FROM EXHAUST | ||
|---|---|---|
| Exhaust temperature | 401.0 | °C |
| Combustion air flow | 0.0 | m³/min |
| Exhaust gas flow | 86.8 | m³/min |
| GENERAL ALTERNATOR DATA | ||
|---|---|---|
| Description | STAMFORD | |
| Alternator model | S5L1D-C | |
| E.P. Power | 600.0 | kVA |
| P.R.P. Power | 550.0 | kVA |
| ALTERNATOR WIRINGS | ||
|---|---|---|
| Connection | Parallel star | |
| Phases | 3F+N | |
| Winding | 12 terminals Winding 311 | |
| Terminal Number | 12 | nr. |
| ALTERNATOR PROTECTION | ||
|---|---|---|
| IP Protection | 23 | |
| ALTERNATOR REGULATOR | ||
|---|---|---|
| Electronic regulator | AS440 | |
| Precision | 1.0 | ± % |
| RADIATOR | ||
|---|---|---|
| Radiator antifreeze capacity | 28.0 | l |
| BASEFRAME DATA | ||
|---|---|---|
| Model | GV151/00/00 | |
| Standard tank | 800 | l |
| CANOPY DATA | ||
|---|---|---|
| Canopy model | GV151 | |
| Silencer model | MSR/a 125 | |
| Silencer outlet diameter | 140.0 | mm |
STANDARD CONTROL PANEL
| CONTROL PANEL DATA | ||
|---|---|---|
| Description | GUARD REVOLUTION AUTO | |
STANDARD ATS
| ATS PANEL DATA |
|---|