D 30 B F4M2011 S1L2-K 208 V 60 HZ
DATASHEET PDF
NEED MORE INFO?
MAIN DATA
| Continuous power (PRP) |
35.70
|
kVA |
| Continuous power (PRP) |
28.56
|
kW |
| Emergency power (E.P.) |
37.50
|
kVA |
| Emergency power (E.P.) |
30.00
|
kW |
| Power factor | 0.8 | cos(fi) |
| Frequency (Hz) | 60 | Hz |
| Voltage (V) | 208 | VAC |
DIMENSIONS AND NOISE
| Width | 960 | mm |
| Length | 1560 | mm |
| Height | 1150 | mm |
| Weight | 770 | kg |
AWESOME FEATURES
1- Industrial diesel engine in genset version with certificate of origin
2- Industrial brushless alternator with AVR
3- Large capacity steel baseframe-fuel tank with level sensor
4- Industrial silencer and coupling flange
5- Electrical panel mounted on board the unit with digital control device installed in metal box
6- Compact for easy handling and use
7- Test report, manuals and electrical drawings supplied
8- World wide after sales service and technical support
Further details on the technical data sheet
2- Industrial brushless alternator with AVR
3- Large capacity steel baseframe-fuel tank with level sensor
4- Industrial silencer and coupling flange
5- Electrical panel mounted on board the unit with digital control device installed in metal box
6- Compact for easy handling and use
7- Test report, manuals and electrical drawings supplied
8- World wide after sales service and technical support
Further details on the technical data sheet
TECHNICAL DATA
| GEN SET GENERAL DATA | ||
|---|---|---|
| Genset model | D 30 B | |
| Connection | Parallel star | |
| DIMENSIONS AND NOISE | ||
|---|---|---|
| Width | 960 | mm |
| Length | 1560 | mm |
| Height | 1150 | mm |
| Weight | 770 | kg |
| ENGINE BASE DATA | ||
|---|---|---|
| Description | DEUTZ | |
| Engine model | F4M2011 | |
| P.R.P. Power | 35.7 | kVA |
| E.P. Power | 37.5 | kVA |
| Cylinders | 4.0 | |
| Speed | 1800.0 | r.p.m. |
| Cubic capacity | 3.1 | l |
| Air intake | Aspirated | |
| Standard voltage | 12.0 | Vdc |
| Optional voltage | 24.0 | Vdc |
| Sae | 3-11½ | |
| BMEP | 740.0 | kPa |
| Cooling | Oil | |
| Fuel Cons. at 100% (E.P.) | 9.4 | l/h |
| Fuel Cons. at 100% (P.R.P) | 8.8 | l/h |
| Fuel Cons. at 75% (P.R.P.) | 6.7 | l/h |
| Fuel Cons. at 50% (P.R.P.) | 4.5 | l/h |
| Fuel Cons. at 25% (P.R.P.) | 3.4 | l/h |
| EMISSIONS | ||
|---|---|---|
| TA Luft | Not available | |
| TA Luft/2 | Not available | |
| EPA | Not available | |
| Stage | Not available | |
| SPEED REGULATION | ||
|---|---|---|
| Electronic regulator | On request | |
| Precision class | G2 | |
| ENGINE DIMENSIONS AND LIQUIDS | ||
|---|---|---|
| Oil quantity | 13.0 | l |
| Engine Antifreeze capacity | 0.0 | l |
| Radiator antifreeze capacity | 0.0 | l |
| Total amount of antifreeze | 0 | l |
| HEAT FROM ENGINE | ||
|---|---|---|
| Heat from radiator | 20.2 | kW |
| Heat from exhaust | 33.1 | kW |
| Heat from radiation | 0.0 | kW |
| HEAT FROM EXHAUST | ||
|---|---|---|
| Exhaust temperature | 660.0 | °C |
| Combustion air flow | 0.0 | m³/min |
| Exhaust gas flow | 7.1 | m³/min |
| GENERAL ALTERNATOR DATA | ||
|---|---|---|
| Description | STAMFORD | |
| Alternator model | S1L2-K | |
| E.P. Power | 46.5 | kVA |
| P.R.P. Power | 42.2 | kVA |
| ALTERNATOR WIRINGS | ||
|---|---|---|
| Connection | Parallel star | |
| Phases | 3F+N | |
| Winding | 12 terminals Winding 311 | |
| Terminal Number | 12 | nr. |
| ALTERNATOR PROTECTION | ||
|---|---|---|
| IP Protection | 23 | |
| ALTERNATOR REGULATOR | ||
|---|---|---|
| Electronic regulator | AS540 | |
| Precision | 1.0 | ± % |
| RADIATOR | ||
|---|---|---|
| Radiator antifreeze capacity | 0.0 | l |
| BASEFRAME DATA | ||
|---|---|---|
| Model | T1 | |
| Standard tank | 160 | l |
| CANOPY DATA | ||
|---|---|---|
| Canopy model | SENZA COFANO | |
| Silencer model | MS 10 | |
| Silencer outlet diameter | 48.0 | mm |
STANDARD CONTROL PANEL
| CONTROL PANEL DATA | ||
|---|---|---|
| Description | GUARD REVOLUTION AUTO | |
STANDARD ATS
| ATS PANEL DATA |
|---|